N2XS2Y (3x) 10kV

Medium-voltage cable, XLPE insulated, copper conductor, polyethylene outersheath

N2XS2Y (3x) 10kV

according VDE 0276 part 620.

  • Variants
  • Downloads
  • Shorter and longer lengths
  • Number of cores

    Cross section conductor

    Technical features Product
    N2XS2Y (3x) 10kV 3X1X240 RM/25 10kV 3 240 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    240 mm²
    Conductor category
    Class 2 = stranded
    Shape of conductor
    Round
    Number of cores
    3
    Core identification
    None
    Laminated sheath
    No
    Fibre optic elements
    No
    Protective conductor
    No
    Inner semi-conducting layer
    Yes
    Outer semi-conducting layer
    Yes
    Screen
    Yes
    Concentric conductor
    None
    Nominal cross section concentric conductor
    25 mm²
    Armouring
    No
    Material outer sheath
    Polyolefin
    Specification material outer sheath
    Polyethylene (PE)
    Colour outer sheath
    Black
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Fca
    Halogen free (acc. EN 60754-1/2)
    Yes
    Flame retardant
    No
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    78 mm
    Weight
    8,615.6
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    20 <=> 70 °C
    Nominal voltage U0
    6 kV
    Nominal voltage U
    10 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    15 x Außen-Ø
    Metal number
    Copper 7761
    Product No. Individual length Pallet unit Packing
    483945 Cut length Ring, Drum
    N2XS2Y (3x) 10kV 3X1X300 RM/25 10kV 3 300 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    300 mm²
    Conductor category
    Class 2 = stranded
    Shape of conductor
    Round
    Number of cores
    3
    Core identification
    None
    Laminated sheath
    No
    Fibre optic elements
    No
    Inner semi-conducting layer
    Yes
    Outer semi-conducting layer
    Yes
    Armouring
    No
    Material outer sheath
    Polyolefin
    Specification material outer sheath
    Polyethylene (PE)
    Colour outer sheath
    Black
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Fca
    Halogen free (acc. EN 60754-1/2)
    Yes
    Flame retardant
    No
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    83 mm
    Weight
    10,322
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    20 <=> 70 °C
    Nominal voltage U0
    6 kV
    Nominal voltage U
    10 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    15 x Außen-Ø
    Metal number
    Copper 9489
    Product No. Individual length Pallet unit Packing
    509348 Cut length Ring, Drum
    N2XS2Y (3x) 10kV 3X1X400 RM/35 10kV 3 400 mm²
    Conductor material
    Copper
    Conductor surface
    Bare
    Nominal cross section conductor
    400 mm²
    Conductor category
    Class 2 = stranded
    Shape of conductor
    Round
    Number of cores
    3
    Core identification
    None
    Laminated sheath
    No
    Fibre optic elements
    No
    Inner semi-conducting layer
    Yes
    Outer semi-conducting layer
    Yes
    Armouring
    No
    Material outer sheath
    Polyolefin
    Specification material outer sheath
    Polyethylene (PE)
    Colour outer sheath
    Black
    Conductive coating
    No
    Longitudinal water blocking conductors
    No
    Longitudinal water blocking screen
    No
    Reaction-to-fire according to EN 13501-6: Class
    Fca
    Halogen free (acc. EN 60754-1/2)
    Yes
    Flame retardant
    No
    Low smoke (acc. EN 61034-2)
    No
    Outer diameter approx.
    89 mm
    Weight
    13,016
    Max. conductor temperature
    90 °C
    Permitted cable outer temperature during assembling/handling
    20 <=> 70 °C
    Nominal voltage U0
    6 kV
    Nominal voltage U
    10 kV
    max. short circuit temperature
    250 °C
    Insulation
    XLPE (VPE)
    Minimum bending radius
    15 x Außen-Ø
    Metal number
    Copper 12702
    Product No. Individual length Pallet unit Packing
    514267 Cut length Ring, Drum
  • Title Language
    Datasheet
    Declaration of Performance
  • We can supply you with shorter lengths and longer lengths of the many cables our company offers, which are available right now in the lengths listed. An additional advantage for you: We offer a price discount on each agreed base price/price without metal on our shorter and longer length cables when purchasing the complete length.

    If you have any queries in this regard, please feel free to get in touch with your usual contact. Together, we will find the right cable solution for your application. You can directly access our current offers for shorter/longer lengths here.

    To shorter and longer lengths "N2XS2Y (3x) 10kV"