N1XZ1-AL
based upon VDE0276-604.. For fixed installation indoors, in air and in concrete. These cables are also suitable for outdoor use, provided they are protected from direct sunlight. Laying in the ground or in water is not permitted.
- Variants
- Downloads
- Shorter and longer lengths
-
Number of cores
Cross section conductor
Technical features Product N1XZ1-AL 4X16 RE 4 16 mm² - Conductor material
- Aluminium
- Conductor surface
- Bare
- Nominal cross section conductor
- 16 mm²
- Conductor category
- Class 1 = solid
- Shape of conductor
- Round
- Number of cores
- 4
- Core identification
- Colour
- Laminated sheath
- No
- Fibre optic elements
- No
- Protective conductor
- No
- Inner semi-conducting layer
- No
- Outer semi-conducting layer
- No
- Screen
- No
- Concentric conductor
- None
- Armouring
- No
- Material outer sheath
- Polyolefin
- Specification material outer sheath
- Polyethylene (PE)
- Colour outer sheath
- Grey
- Conductive coating
- No
- Longitudinal water blocking screen
- No
- Reaction-to-fire according to EN 13501-6: Class
- Eca
- Halogen free (acc. EN 60754-1/2)
- Yes
- Flame retardant
- In accordance with IEC/EN 60332-1-2
- Low smoke (acc. EN 61034-2)
- Yes
- Outer diameter approx.
- 18 mm
- Weight
- 441.84
- Max. conductor temperature
- 90 °C
- Permitted cable outer temperature during assembling/handling
- -5 <=> 70 °C
- Permitted cable outer temperature after assembling without vibration
- -40 <=> 70 °C
- Nominal voltage U0
- 0.6 kV
- Nominal voltage U
- 1 kV
- max. short circuit temperature
- 250 °C
- Insulation
- XLPE (VPE)
- Minimum bending radius
- 12 x Außen-Ø
Product No. Individual length Pallet unit Packing 501090 Cut length Ring, Drum 507320 250 m 1,000 Drum N1XZ1-AL 4X25 RE 4 25 mm² - Conductor material
- Aluminium
- Conductor surface
- Bare
- Nominal cross section conductor
- 25 mm²
- Conductor category
- Class 1 = solid
- Shape of conductor
- Round
- Number of cores
- 4
- Core identification
- Colour
- Laminated sheath
- No
- Fibre optic elements
- No
- Protective conductor
- No
- Inner semi-conducting layer
- No
- Outer semi-conducting layer
- No
- Screen
- No
- Concentric conductor
- None
- Armouring
- No
- Material outer sheath
- Polyolefin
- Specification material outer sheath
- Polyethylene (PE)
- Colour outer sheath
- Grey
- Conductive coating
- No
- Longitudinal water blocking screen
- No
- Reaction-to-fire according to EN 13501-6: Class
- Eca
- Halogen free (acc. EN 60754-1/2)
- Yes
- Flame retardant
- In accordance with IEC/EN 60332-1-2
- Low smoke (acc. EN 61034-2)
- Yes
- Outer diameter approx.
- 22 mm
- Weight
- 636.95
- Max. conductor temperature
- 90 °C
- Permitted cable outer temperature during assembling/handling
- -5 <=> 70 °C
- Permitted cable outer temperature after assembling without vibration
- -40 <=> 70 °C
- Nominal voltage U0
- 0.6 kV
- Nominal voltage U
- 1 kV
- max. short circuit temperature
- 250 °C
- Insulation
- XLPE (VPE)
- Minimum bending radius
- 12 x Außen-Ø
Product No. Individual length Pallet unit Packing 501069 Cut length Ring, Drum N1XZ1-AL 4X50 SE 4 50 mm² - Conductor material
- Aluminium
- Conductor surface
- Bare
- Nominal cross section conductor
- 50 mm²
- Conductor category
- Class 1 = solid
- Shape of conductor
- Sector-shaped
- Number of cores
- 4
- Core identification
- Colour
- Laminated sheath
- No
- Fibre optic elements
- No
- Protective conductor
- No
- Inner semi-conducting layer
- No
- Outer semi-conducting layer
- No
- Screen
- No
- Concentric conductor
- None
- Armouring
- No
- Material outer sheath
- Polyolefin
- Specification material outer sheath
- Polyethylene (PE)
- Colour outer sheath
- Grey
- Conductive coating
- No
- Longitudinal water blocking screen
- No
- Reaction-to-fire according to EN 13501-6: Class
- Eca
- Halogen free (acc. EN 60754-1/2)
- Yes
- Flame retardant
- In accordance with IEC/EN 60332-1-2
- Low smoke (acc. EN 61034-2)
- Yes
- Outer diameter approx.
- 25 mm
- Weight
- 895.15
- Max. conductor temperature
- 90 °C
- Permitted cable outer temperature during assembling/handling
- -5 <=> 70 °C
- Permitted cable outer temperature after assembling without vibration
- -40 <=> 70 °C
- Nominal voltage U0
- 0.6 kV
- Nominal voltage U
- 1 kV
- max. short circuit temperature
- 250 °C
- Insulation
- XLPE (VPE)
- Minimum bending radius
- 12 x Außen-Ø
Product No. Individual length Pallet unit Packing 507184 Cut length Ring, Drum N1XZ1-AL 4X 95 SE 4 95 mm² - Conductor material
- Aluminium
- Conductor surface
- Bare
- Nominal cross section conductor
- 95 mm²
- Conductor category
- Class 1 = solid
- Shape of conductor
- Sector-shaped
- Number of cores
- 4
- Core identification
- Colour
- Laminated sheath
- No
- Fibre optic elements
- No
- Protective conductor
- No
- Inner semi-conducting layer
- No
- Outer semi-conducting layer
- No
- Screen
- No
- Concentric conductor
- None
- Armouring
- No
- Material outer sheath
- Polyolefin
- Specification material outer sheath
- Polyethylene (PE)
- Colour outer sheath
- Grey
- Conductive coating
- No
- Longitudinal water blocking screen
- No
- Reaction-to-fire according to EN 13501-6: Class
- Eca
- Halogen free (acc. EN 60754-1/2)
- Yes
- Flame retardant
- In accordance with IEC/EN 60332-1-2
- Low smoke (acc. EN 61034-2)
- Yes
- Outer diameter approx.
- 33 mm
- Weight
- 1,612
- Max. conductor temperature
- 90 °C
- Permitted cable outer temperature during assembling/handling
- -5 <=> 70 °C
- Permitted cable outer temperature after assembling without vibration
- -40 <=> 70 °C
- Nominal voltage U0
- 0.6 kV
- Nominal voltage U
- 1 kV
- max. short circuit temperature
- 250 °C
- Insulation
- XLPE (VPE)
- Minimum bending radius
- 12 x Außen-Ø
Product No. Individual length Pallet unit Packing 575213 Cut length Ring, Drum N1XZ1-AL 4X150 SE 4 150 mm² - Conductor material
- Aluminium
- Conductor surface
- Bare
- Nominal cross section conductor
- 150 mm²
- Conductor category
- Class 1 = solid
- Shape of conductor
- Sector-shaped
- Number of cores
- 4
- Core identification
- Colour
- Laminated sheath
- No
- Fibre optic elements
- No
- Protective conductor
- No
- Inner semi-conducting layer
- No
- Outer semi-conducting layer
- No
- Screen
- No
- Concentric conductor
- None
- Armouring
- No
- Material outer sheath
- Polyolefin
- Specification material outer sheath
- Polyethylene (PE)
- Colour outer sheath
- Grey
- Conductive coating
- No
- Longitudinal water blocking screen
- No
- Reaction-to-fire according to EN 13501-6: Class
- Eca
- Halogen free (acc. EN 60754-1/2)
- Yes
- Flame retardant
- In accordance with IEC/EN 60332-1-2
- Low smoke (acc. EN 61034-2)
- Yes
- Outer diameter approx.
- 39 mm
- Weight
- 2,294.2
- Max. conductor temperature
- 90 °C
- Permitted cable outer temperature during assembling/handling
- -5 <=> 70 °C
- Permitted cable outer temperature after assembling without vibration
- -40 <=> 70 °C
- Nominal voltage U0
- 0.6 kV
- Nominal voltage U
- 1 kV
- max. short circuit temperature
- 250 °C
- Insulation
- XLPE (VPE)
- Minimum bending radius
- 12 x Außen-Ø
Product No. Individual length Pallet unit Packing 562398 Cut length Ring, Drum -
We can supply you with shorter lengths and longer lengths of the many cables our company offers, which are available right now in the lengths listed. An additional advantage for you: We offer a price discount on each agreed base price/price without metal on our shorter and longer length cables when purchasing the complete length.
To shorter and longer lengths "N1XZ1-AL"
If you have any queries in this regard, please feel free to get in touch with your usual contact. Together, we will find the right cable solution for your application. You can directly access our current offers for shorter/longer lengths here.